
The constant volume regulator is an element placed inside the duct in order to obtain a constant flow within a pressure range from 50 to 250 Pascals.
It is used in air conditioning or ventilation systems either in extraction or blowing mode.
Regulator Diameter |
N/A 6 Inch |
Setting |
N/A RDR Ø 100 + 2 cales |
Maximum Temperature |
N/A 60 ºC |
Material |
N/A
Plastic (Classified M1) |
Flow Range |
N/A 30-60 CFM |
Set Flow |
N/A 60 CFM |
Dimension D1 |
N/A 145 mm |
Dimension D2 |
N/A 148 mm |
Dimension L |
N/A 91 mm |
Components |
N/A Air Flow Setting Cale (According to the Air Flow) Piece of Regulation Regulator Casing Screw to Fix the Air Flow Sleave with Lip Seal |
Sound Power Level at 60 Cubic Meter Per Hour (m³/h) Flow and 50 Pascal (Pa) Pressure |
N/A 32 dBA |
Sound Power Level at 60 Cubic Meter Per Hour (m³/h) Flow and 100 Pascal (Pa) Pressure |
N/A 37 dBA |
Sound Power Level at 60 Cubic Meter Per Hour (m³/h) Flow and 150 Pascal (Pa) Pressure |
N/A 39 dBA |
Sound Power Level at 60 Cubic Meter Per Hour (m³/h) Flow and 200 Pascal (Pa) Pressure |
N/A 42 dBA |
Sound Power Level at 75 Cubic Meter Per Hour (m³/h) Flow and 50 Pascal (Pa) Pressure |
N/A 32 dBA |
Sound Power Level at 75 Cubic Meter Per Hour (m³/h) Flow and 100 Pascal (Pa) Pressure |
N/A 37 dBA |
Sound Power Level at 75 Cubic Meter Per Hour (m³/h) Flow and 150 Pascal (Pa) Pressure |
N/A 40 dBA |
Sound Power Level at 75 Cubic Meter Per Hour (m³/h) Flow and 200 Pascal (Pa) Pressure |
N/A 42 dBA |
Sound Power Level at 90 Cubic Meter Per Hour (m³/h) Flow and 50 Pascal (Pa) Pressure |
N/A 32 dBA |
Sound Power Level at 90 Cubic Meter Per Hour (m³/h) Flow and 100 Pascal (Pa) Pressure |
N/A 38 dBA |
Sound Power Level at 90 Cubic Meter Per Hour (m³/h) Flow and 150 Pascal (Pa) Pressure |
N/A 41 dBA |
Sound Power Level at 90 Cubic Meter Per Hour (m³/h) Flow and 200 Pascal (Pa) Pressure |
N/A 44 dBA |
Important |
N/A
|
Presentation |
N/A
The self-adjusting flow regulator RDR can be adjusted on sites according to the requested air flow. |
Adjustment |
N/A
Before setting the regulator, it's necessary to calibrate the flow:
|
Installation |
N/A
The flow regulators are simply fitted into vertical or horizontal ducts. On the horizontal duct, respect the mention «DOWN» indicated at the front of the product. A leap seal ensures the airtightness. |
Characteristics |
N/A
The curves show the flow variations in m³/h of RDR Ø 150, 160 and 200 mm in extraction according to the difference in of pressure in Pascal (pressure range of 50 to 250 Pa). The values given are averages which may vary of 5 % either way. Flow regulators are characterized by their noise level dB(A). |